chinese    english
 
    This kind of Resistance-reduce-agent is composed of many ingredients, including electrolyte, curing agent, lubricant, electro-conductive cement and stuffing materials. As one excellent electric conductor, it is used between grounding part and earth. On the one hand, it can be closely connected to metal grounding to form enough current surface; on the other hand, it can infiltrate into soil near it to lower resistance and form one low resistance district around grounding parts.
 
 
     
 
Name: @
Pass:
 
 
11.Over Pressure Thunder Protection Device for Signal of Information Network

■ QPRS series D type connecting interface surge protection device
It is suitable to the transmitting signal equipment of D type connecting interface type; the type of transmitting connecting interface includes RS485, RS422 and RS232 etc, which is applicable for the industrial automatic system especially for preventing the damage caused because the hoist of electric potential or the over-load of circuit induction.

 
 Type
QPRS232-25
QPRS232-15
QPRS232-9
QPRS485-9
  Order No.  5220  5221  5222  5223
  Frequency  20KHz  20KHz  20KHz  20KHz
  Tie-in (D-Sub)  25 pin  15 pin  9 pin  9 pin
  Protected core line 2,3,4,5,6,7,8,20 2,3,4,5 2,3,4,5 4,5,8,9,6(power)
  Zero Potential  7  5  5  3
  Grade of Protection Voltage  30V  30V  30V  18V
 Max. Discharge Current of Every Core (8/20 μ s)  180A  180A  180A  120A

■ QPL series connection type signal surge protection device
It is suitable for three-grade protection of communications system, computer system and automatic control loop system (like RS232, RS422 and RS485) with many good characters such as large discharge current, low outputting residual voltage, long using life and convenient installation etc.

 Type    2 line QPL-6 QPL-12 QPL-24 QPL-48 QPL-120
  Order No.  5240  5241  5242  5243  5244
  Rating Working Voltage Un  6V  12V  24V  48V  120V
  Rating Working Current ln  300mA  300mA  300mA  300mA  300mA
  Static Threshold Voltage (100V/s)  9V  18V  36V  75V  200V
  Dynamic Voltage (1KV/μs)  ≤12V  ≤22V  ≤55V  ≤120V  ≤300V
  Rating Discharge Current (8/20μs)  10KA  10KA  10KA  10KA  10KA
 Frequency Width (inserting loss ≤ -0.4dB)  ≤2MHz  ≤2MHz  ≤2MHz  ≤2MHz  ≤2MHz
  Material   Pale Automatic Nonflammable Plastic (UL94-Vo)
  External Dimension  17.5×90×17mm
  Lead Fixation (lead section)  Bolt Fixation ( ≤ 4mm2)
  Function Characteristic
Application

 three-grade protection; it will intermit if product aging; crust is anti-flame; mounting rail installation
simulation quantity, digital quantity, control signal

  Type Extension  the corresponding type of working current ln = 2A is QPL-A