chinese    english
 
    This kind of Resistance-reduce-agent is composed of many ingredients, including electrolyte, curing agent, lubricant, electro-conductive cement and stuffing materials. As one excellent electric conductor, it is used between grounding part and earth. On the one hand, it can be closely connected to metal grounding to form enough current surface; on the other hand, it can infiltrate into soil near it to lower resistance and form one low resistance district around grounding parts.
 
 
     
 
Name: @
Pass:
 
 
13.Surge Restrain Anti-thunder Cabinet for Power Distribution Network

QSD series surge restrain protection device adopts the most advanced surge identification technique and latest machining craftwork in world at present, which is applicable for the communication computer office, the power equipment of communications station and the power equipment of military affairs chain of command and other main equipments.

Specs & Type
QSD125A-2S
QSD125A-4S
QSD125-2S
QSD125-4S
QSD125Y-2S
QSD125Y-4S
 Order No.  5400  5410  5402  5403  5404  5405
 Uo(V)  220  220  220  220  220  220
 Uc(V)  275  275  275  275  440  440
 ln(KA)  25  25  25  25  25  25
 lmax(KA)  50  50  50  50  50  50
 Up(KV)  1.4  1.4  1.4  1.4  1.0  1.0
 lie(μA)  <5  <5  <5  <5  <0.5  <0.5
 Answering Time  <5ns
  Working Environment  -40℃-80℃
  Relative Humidity  ≤95%
  Installation Condition  Earthing Resistance < 10 Ω
  External Dimension  100×300×400(mm)
 Connecting Lead Specs  ≥6mm
 Application Single-phase Power Supply Three-phase Power Supply Single-phase Power Supply Three-phase Power Supply Single-phase Power Supply Three-phase Power Supply
 
Scope of Application
 
two, three grade protection for main power equipment
two, three grade protection for main power equipment in region with heavy thunderstorm
  Equipment
Lighting Alarm
Counter
Audible and Visual Alarm Signal Connecting Interface

Surge Distinguish
Counter
Audible and Visual Alarm
Signal Connecting Interface

 

Specs & Type
QSD150A-2S
QSD150A-4S
QSD150-2S
QSD150-4S
QSD150Y-2S
QSD150Y-4S
Order No.  5420  5421  5422  5423  5424  5425
 Uo(V)  220  220  220  220  220  220
 Uc(V)  275  275  275  275  440  440
 ln(KA)  50  50  50  50  50  50
 lmax(KA)  100  100  100  100  100  100
 Up(KV)  1.5  1.5  1.5  1.5  1.5  1.5
 lie(μA)  <5  <5  <5  <5  <0.5  <0.5
Answering Time
 <5ns
Working Environment
 -40℃-80℃
Relative Humidity
 ≤95%
Installation Condition
 Earthing Resistance < 10 Ω
External Dimension
 100×300×400(mm)
Connecting Lead Specs
 ≥6mm
Application
Single-phase Power Supply Three-phase Power Supply Single-phase Power Supply Three-phase Power Supply Single-phase Power Supply Three-phase Power Supply
Scope of Application
one, two grade protection for main power equipment

one, two grade protection for main power equipment in region with heavy thunderstorm

Equipment
Lighting Alarm

Counter
Audible and Visual Alarm Signal Connecting Interface


Surge Distinguish
Counter
Audible and Visual Alarm
Signal Connecting Interface

NEXT >>