chinese    english
 
    This kind of Resistance-reduce-agent is composed of many ingredients, including electrolyte, curing agent, lubricant, electro-conductive cement and stuffing materials. As one excellent electric conductor, it is used between grounding part and earth. On the one hand, it can be closely connected to metal grounding to form enough current surface; on the other hand, it can infiltrate into soil near it to lower resistance and form one low resistance district around grounding parts.
 
 
     
 
Name: @
Pass:
 
 
1. Resistance-reducing Agent

一、Principle of Resistance Reduction 
  This resistance reduction is comprises of diversiform ingredient including electrolyte, firming agent, lube, filling material. As a good conductor, It can impinge on the  metallic earth to form circulating surface of current as well as infiltrate into the soil to form an area of low resistance around the grounding body.
二、usage scale
  It is widely used for grounding device in all walks of national economy such as electricity, telecom, architecture, broadcast, television, railway, highway, voyage, water carriage, national defence &war industry, metallurgy&mine,  coal, petroleum, chemical industry, textile, medicine &sanitation, culture&education, publication&printing.
三、Main Technical Parameter
  1、dropping resistivity:40%-95%(more resistivity of soil leads to more resistance dropping)
  2、stability&long residual action: The period of validity of resistance reduction is 10-20 years.
  3、It has stronger water retention, water absorption.
  4、Other performance index: referring to following table:
  Summary Table of Test for Resistance Reduction
serial number
name of testing item
requirements
trial value
conclusion
1
resistivity measuring test at room temperature
assessing  of chemical&physical performance
P≤5Ω.m
ρ=0.5Ω.m△
eligibility
2
a、water loss test
after-test
ρ=0.6Ω.m
pass
b、hot-cold alternating test
P≤5Ω.m
ρ=0.48Ω.m
pass
c、wet steep test
ρ=0.6Ω.m
pass
3
tolerance for impulse current test
△R%≤20%
△R%≤2.4%
pass
4
tolerance for power current test
△R%≤20%
△R%≤-27%
pass
5
PH value

measuring test

PH value range from 7-12
PH=8
eligibility
resistance reduction-steel grounding body
corrosion test
average corrosion rate on surface
≤0.03mm/year
average corrosion on surface(mm/year)range(mm/year)
 
6
pure resistance reduction-steel grounding body
 
0.0029round steel
0.0024-0.0030
pass
corrosion test
 
0.0030flat steel
0.0018-0.0030
pass
 
 
0.0021zinc plated round steel
0.0020-0.0025
pass
 
 
0.0026zinc plated round steel
0.0021-0.0028
pass